Approach direction
Can be adjusted in 90° steps
Short circuit monitoring
The switch generates its own clock signal on the output cables OA/OB. Pay attention to this aspect when connecting to control systems and relays.
Multicode evaluation
Every suitable actuator is detected by the switch.
Category according to EN 13849-1
Due to two redundantly designed semiconductor outputs (safety outputs) with internal monitoring suitable for:
- Category 4/PL e according to EN 13849-1
Important: To achieve the stated category in accordance with EN ISO 13849-1, both safety outputs (OA and OB) must be evaluated.
LED indicator
STATE | Status LED |
DIA | Diagnostics LED |
Additional connections
OUT | Monitoring output (semiconductor) |
RST | Reset input |
Typical operating distance
With actuator CES-A-BBA and CES-A-BCA
For a side approach direction for the actuator and safety switch, a minimum distance of s = 4 mm must be maintained so that the operating distance of the side lobes is not entered.
With actuator CES-A-BPA
For a side approach direction for the actuator and safety switch, a minimum distance of s = 6 mm must be maintained so that the operating distance of the side lobes is not entered.
With actuator CES-A-BRN
For a side approach direction for the actuator and safety switch, a minimum distance of s = 6 mm must be maintained so that the operating distance of the side lobes is not entered.
Connector assignment
Plug connector (view of connection side) | Pin | Designation | Function | Conductor coloring of connection cable |
---|---|---|---|---|
1 | IB | Enable input for channel 2 | WH | |
2 | UB | Power supply, DC 24 V | BN | |
3 | OA | Safety output, channel 1 | GN | |
4 | OB | Safety output, channel 2 | YE | |
5 | OUT | Monitoring output | GY | |
6 | IA | Enable input for channel 1 | PK | |
7 | 0V | Ground, DC 0 V | BU | |
8 | RST | Reset input | RD |
Housing material | Plastic, PBT |
Weight | |
Net | 0,12 kg |
Ambient temperature | -20 … 55 °C |
Degree of protection | IP67 |
Resilience to vibration | In acc. with EN IEC 60947-5-2 |
Mounting distance | min.40 mm |
Installation orientation | Any |
Tightening torque | |
Fixing screws | max.1 Nm |
Ready delay | 10 s |
Switching frequency | max.1 Hz |
Connection | M12 plug connector, 8-pin |
Electrical connection ratings
Operating voltage DC | |
UB | 24 V DC 15% … 15% Reverse polarity protected, regulated, residual ripple < 5%, PELV |
Current consumption | |
No load on outputs | max.50 mA |
Fusing | |
External (operating voltage) | 0,25 … 8 A |
Rated insulation voltage Ui | 300 V |
Rated impulse withstand voltage Uimp | max.1,5 kV |
EMC protection requirements | In acc. with EN IEC 60947-5-3 |
Degree of contamination (external, according to EN 60947-1) | 3 |
Switch-on time | |
Safety outputs | max.400 ms |
Safety class | III |
Risk time according to EN 60947-5-3 | |
Delay per device | 5 ms |
Single device | max.260 ms |
Monitoring output OUT | |
Type of output | p-switching, short circuit-proof |
Switching current | max.200 mA |
Output voltage | 0,8 x UB … UB V DC |
Safety outputs OA/OB | |
Test pulses | max.1 ms |
Type of output | Semiconductor outputs, p-switching, short circuit-proof |
Switching current | |
per safety output | 1 … 400 mA |
Output voltage | |
HIGH U(OA) / U(OB) | UB-1,5 … UB V DC |
LOW U(OA) / U(OB) | 0 … 1 V DC |
Utilization category according to EN 60947-5-2 | |
DC-13 | 24V 400mA |
Rated conditional short-circuit current | max.100 A |
Off-state current Ir | max.0,25 mA |
Discrepancy time | max.10 ms |
Work area
Repeat accuracy R | ? 10 |
Other
For the approval according to UL the following applies | Operation only with UL class 2 power supply, or equivalent measures |
Reliability values according to EN ISO 13849-1
Monitoring of the safety guard position | |
Category | 4 |
Performance Level | PL e |
PFHD | 2.1 x 10-9 |
Mission time | 20 |
In combination with Actuator CES-A-BBAOperating distance
Switch-on distance | 18 mm |
Assured switch-off distance Sar | max.45 mm |
Assured operating distance Sao | min.15 mm |
Switching hysteresis | min.1 mm |
In combination with Actuator CES-A-BPAOperating distance
Switch-on distance | 22 mm |
Assured switch-off distance Sar | max.58 mm |
Assured operating distance Sao | min.18 mm |
Switching hysteresis | min.1 mm |
In combination with Actuator CES-A-BRN-100251Operating distance
Switch-on distance | 27 mm |
Assured switch-off distance Sar | max.75 mm |
Assured operating distance Sao | min.20 mm |
Switching hysteresis | 3 mm |
In combination with Actuator CES-A-BDA-18-156935Operating distance
Switch-on distance | 19 mm |
Assured switch-off distance Sar | max.45 mm |
Assured operating distance Sao | min.10 mm |
Switching hysteresis | min.1 mm |